Janitza Module 800-CT8-LP
| Type of manufacturer: | Modul 800-CT8-LP |
|---|---|
| Manufacturer Art. No.: | 5231234 |
| Art. Nr.: | 16969 |
| Pieces per package unit: |
|
| Accessory type: | Data-logger |
Prices are only visible to business customers upon successful registration.
- New
Product number:
16969
Description
Janitza Module 800-CT8-LP
The 800-CT8-LP current measurement module expands the 800 Series energy analysers to include 8 low-power current measurement inputs for current transformers with a 333 mV output.
The inputs are divided into two blocks of four. This means that one module can measure two three-phase outputs (L1, L2, L3, N) or several single-phase outputs. As no secondary current flows, you do not need short-circuit clamps, making installation safer. At just 1 TE wide, the module fits even into tight distribution panels and can be easily retrofitted into existing local distribution substations. Power is supplied via the JanBus from the base unit.
Product benefits
- Safe: no short-circuit terminals required, greater safety during installation
- Space-saving: only 1 TE wide, ideal for retrofitting
- Cost-effective: compatible with low-cost 333 mV current transformers
- Precise: phase current accuracy class 0.2
- Easy installation: click-in system with no external cabling to the base unit
- Scalable: multiple modules can be combined, up to 96 current measurement inputs per system
Product features
- Current measurement inputs: 8 (2 x 4), for low-power 333 mV current transformers
- Input signal: 0 – 400 mV, input impedance 230 kΩ
- Overload: 1 V for 1 s
- Accuracy: phase current Class 0.2, active power Class 0.5, active energy Class 0.5S (IEC 62053-22)
- Resolution: 16 bits
- Sampling frequency: 6.8 kHz
- Current harmonics: 1st – 15th (odd)
- Mains frequency: 40 – 70 Hz
- Power supply: 24 V via JanBus from the base unit
- Interface: JanBus via bus connector
- Space requirement: 1 module slot
- Mounting type: Top-hat rail mounting (35 mm, EN 60715)
- Protection rating: IP20, IK07, Protection Class II
- Operating temperature: -10 °C to +55 °C
- Net weight: approx. 73 g
- Device dimensions: 18 mm x 90 mm x 76 mm (1 TE)
-
Matching accessories